Abstract

Analysis by using Fluent® has been carried out to investigate the pressure drop and heat transfer of single phase flow (Reynolds number ranging from 2.0×104 − 1.4×105) in a 2 meter long of rifled tube and smooth tube which are heated at the outer wall at constant temperature. The rifled tube or also known as spiral internally ribbed tube which is used in this investigation has an outside diameter 45.0 mm and inside equivalent diameter of 33.1 mm while the smooth tube has an outside diameter 45.0 mm and inside diameter 34.1 mm. The working fluid that is used in this investigation is water. In this analysis, realizable k-epsilon model has been chosen to solve the fully developed turbulence flow in both the tubes. The result from simulation shows that the pressure drop in rifled tube is about 1.69-2.0 times higher than in the smooth tube while the heat transfer coefficient of water in the rifle tube is 0.97-1.27 times than in the smooth tube. The high pressure drop and heat transfer coefficient in rifled tube comparing to smooth tube is due to the helical rib in the rifled tube which not only acted as rough surface, but also causes swirling effect near the wall which enhance heat transfer. The present study has proved that although the rifled tube produces high pressure drop but it is good in heat transfer enhancement through the ratio of heat flux to the pumping power. Correlations have been proposed for the single phase friction factor and Nusselt number of the rifled tube.