Abstract

High Impedance Faults (HIFs) occur by the contact between an energized conductor and a high impedance surface. Due to the low fault current level, HIFs cannot be detected by conventional protection and there is no fully efficient solution to this problem. HIF detection methods often extract metrics using signal processing techniques, such as Fourier Transform, Wavelet Transform, Stockwell Transform, and Mathematical Morphology. However, these techniques are applied under specific conditions, which hinders comparative and critical analyses among them. Therefore, this paper presents a critical review of HIF detection methods based on the aforementioned techniques, and also shows a detailed investigation of the performance of the metrics commonly used with them. To do this efficiently, the authors proposed a set of assessment indices based on the ratio between the metrics’ characteristics and another one based on the repeating of the metrics features. The proposed indices revealed that some of these metrics fail to distinguish HIF from other typical occurrences in power distribution systems, and their performances are negatively affected by the fault location and by the existence of noise in the measurements. Additionally, the results showed a need to specify system conditions in which any HIF detection technique is valid.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call