Abstract
We present a simulation analysis of closed Rankine cycle convective heat pump driers in which the product air recirculation ratin within the chamber is high. The configurations include driers with both external and internal refrigerant evaporators. The effects of modifications to basic designs are examined and real plant details are added in successive stages. Throughout the study the efficiency of each system is related to the second law loss mechanisms discussed by Carrington and Baines (1988). A detailed audit of exergy losses is presented for two driers in particular situations using data based on operational timber driers. The simulation results illustrate the need for the drier control strategy to take advantage of the performance characteristics of the heat pump drier. In addition, it is important to carefully match fans and heat exchangers to the drier requirements because the fan power will often be comparable with the compressor input.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.