Abstract

This paper analyzes the influence of the converter droop settings and the dc grid network topology on the power sharing in a dc grid based on voltage source converter high voltage direct current technology. The paper presents an analytical tool to study the effect of the droop control settings on the steady-state voltage deviations and power sharing after a converter outage, thereby accounting for dc grid behavior. Furthermore, an optimization algorithm is developed, taking into account two conflicting optimization criteria. The simulation results show that, when selecting appropriate values for the converter gains, a tradeoff has to be made between the power sharing and the maximum allowable dc voltage deviation after an outage.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.