Abstract

In order to find out partial discharge (PD) phenomena in the cable joint due to the poor workmanship during the installation, the relationship between PD inception voltages and joint defects was investigated. For the purpose, in the joint of 22.9kV CNCV cables, electric fields were calculated for various semiconductive layer wrong positioning (WP) defects. And, PDIV were investigated through the experiments and compared with the results of electric field analysis. In all WP defect cases, the PD inception field calculated using measured PDIVs was similarly shown to be the average value of 1.84kV/mm. In addition, the calculated PDIV and the measured PDIV were almost equal, from the PDIV calculation using maximum electric fields and the measured PDIV for the normal case. Throughout this study, it is possible to analyze WP defects due to the poor workmanship and to establish better joint design for the distribution grade extruded cable system.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.