Abstract

A programme of work involving the measurement of ventilation rates, air velocities and temperatures has been completed within a naturally ventilated auditorium in the Queens Building, De Montfort University. Measurements have been recorded for 'winter', 'mid-season' and 'summer' conditions, and average occupancy levels. Measurements carried out in 'winter' and 'mid-season' indicate that the predominant ventilation driving force is the stack effect. However, current control settings of fresh air inlets allow too great a free area to be produced, which causes high room air velocities with associated low temperatures, resulting in high discomfort levels for occupants seated in line with external openings. Results for 'summer' external conditions on particular dates indicate that ventilation rates are driven largely by wind-induced effects, which can be much higher than buoyancy-driven flows. Internal ceiling and wall surface temperatures show little variations with time, owing to the heavyweight nature of the building structure and its exposed areas.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.