Abstract

This paper presents results of simulation studies of the influence of methods of grounding the stator winding of the unit-connected generator neutral on the operating conditions of a 100-percent ground-fault protection excited by the third-harmonic voltage ratio in the generator neutral and at its terminals. The analysis was performed for a generator with the neutral grounded through a ground-fault neutralizer, a third-harmonic stop filter, a resistor, and a capacitive voltage divider. The influence of the parameters of the particular elements of the grounding circuits on the voltage-feeding measuring element of the protection was determined. The capacitance to ground of the generator breakers was taken into account. The simulations were run for 1110-MVA unit-connected generator at ground faults along the whole length of the generator stator winding. It has been found that the method of grounding the generator neutral and the parameter of the grounding elements significantly influences the operating conditions of this protection. It is shown that through the proper selection of these parameters, the ground-fault protection of whole stator winding, counting from the generator neutral to the terminals is ensured.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.