This paper presents an analysis of solid insulation perma-wood ring failure of 315MVA, 400/220/33kv transformer at site and its on-site replacement procedure in details. In power transformers, insulation of high voltage (HV), low voltage (LV) and tap windings are designed in which all the insulation co-ordination i.e. phase to phase and phase to earth, partial discharge and stray & eddy current losses are considered and calculated. The basic insulations i.e. perma wood ring insulation, lead insulation, Inter turn insulation , insulation between respective winding , insulation with respect to tank , yoke & core etc are designed and placed as per voltage level of transformer. For uniform pressing of winding coils, Perma wood ring are used in each phase of core coil assembly (active part) of transformer for uniform pressing of winding coil and also for providing insulation between coil & core clamp.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.