Abstract

The off-line and on-line partial discharge (PD) in the stator winding of three high-voltage (HV) motors (1,400 HP, 6.6 kV) is measured and analyzed in this paper. The off-line PD is measured at high values between 24,300 ~ 36,100 pC after 18 years of motor operation. Spare replacement motors were not available for testing the degree of deterioration of the stator windings in standstill status. Therefore, on-line periodic analysis was conducted to monitor the trend of PD after installing a ceramic sensor (110 pF, 6.6 kV) in the terminal box for each phase of each motor. In the stator winding of the No.1 and No.2 HV motors, which showed high magnitudes of off-line PD and low magnitudes of on-line PD, defects are expected to appear in the neutral end of the winding. On the contrary, in the stator windings of the No.3 HV motor, which exhibits high off-line and on-line PD magnitude, defects are expected to appear in the terminal end of the winding where a voltage close to the phase voltage is applied.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.