Abstract
An analysis is made on the non-selective actuation of the differential protection of busbars with a voltage of 110 kV of an electrical distribution system substation in the transition mode of an external two-phase short circuit. The protection effect is found to be due to the saturation of the transformer cores of class P current included in fault-free phases. Methods are also analyzed to ensure the correct operation of protection in the considered mode, and methods for calculating the protection parameters at which these methods are workable are proposed.
Published Version
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.