Abstract

This paper presents the measured results and harmonics generated by a commercial wind power generation system (WPGS) consisting of four identical 660 kW wind-turbine induction generators (WTIGs). The studied WPGS is connected to an 11.4 kV bus inside a large petroleum-chemical industrial mill located around the middle coast of Taiwan. The field measured results of total harmonic distortion (THD) in the current and voltage contributed by the WPGS are analyzed using a probabilistic approach since the measured quantities are random in nature. The IEEE harmonic limit is employed to check the level of penetration due to the WPGS. It is found that the THD in the current at the point of common coupling (PCC) connecting four WTIGs is larger than the 5% limitation of IEEE.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.