Abstract
This paper presents the analysis of leakage current characteristics of outdoor polymer insulator due to pollution under wet conditions. In this work, laboratory based pollution performance tests were carried out on 11kv silicon rubber polymer insulator under AC voltage at different pollution levels with sodium chloride as a contaminant. Leakage current waveforms during the experimental studies were measured. Normally FFT spectrum estimation method used to find the harmonic spectrum in the leakage currents. But this method suffers from the major problem of resolution. So in this paper a higher order spectrum estimation method (Min-Norm) employed to understand the frequency domain characteristics of the leakage current signal. The results of the harmonic spectrum shows that has a good resolution than FFT spectrum and Reported results of this preliminary study on 11kv silicon rubber insulator shows that development of flashover due to pollution could be easily identified from the analysis of harmonic contents of leakage current signal.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.