Abstract

In this paper, the integration of multi-terminal HVDC systems to weak power grids is analysed under different grid strengths and control methods. In this paper, a modular multi-level converter based MTDC network is considered. The analysis showed the importance of voltage control of DC network. The voltage control of DC network needs to be performed from the converter station connected to the strongest AC network. Furthermore, the analysis shows that either droop or PI control can be used for controlling the DC voltage of the MT DC network connected to one or more weak grids. However, the droop control of DC voltage provides faster response compared to PI with larger steady state error. Finally, the analysis showed that the MMC - based MTDC is capable of ride-through unbalanced AC side faults even if the faults occur in a weak grid.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.