Abstract

Abstract The first part of paper deals with the base information about diagnostics of power transformers. The second part of paper deals use of method of frequency domain spectroscopy (FDS) for traction transformer. This method is used in analysis insulating condition and its solution has scientific importance for analysis of power transformer with system of oil-paper. It was found, that the results of these tests are highly impacted by the operating temperature during the experimental measurement. Finally, the paper presents experimental results of this diagnostic measurement for a real traction transformer at different operating temperatures and states (with oil and without). It has been found, that moisture and conductivity between paper and oil in an insulating system are highly dependent from temperature.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.