Abstract

When DC transmission system adopts monopole earth or bipolar imbalance operation mode, the DC grounding electrode will inject large amount of current into the earth, and then disturb the running of the power grid. In view of the influence which is created by DC transmission system in Guangdong power grid, this paper derived the mathematical expressions of the transformer neutral point current after creating a calculation model, and concluded the main influence factors; The subject applied the linear regressing analysis theory to calculate the regression equations of transformers so that the slope of the regressing equation can be used to estimate the influence scope of grounding DC. Finally it concludes that: transformer neutral point current and the power transmitted by DC system has positive correlation; For ±800kV DC Chu Sui, the transformers ,which is more than 80 km away from DC grounding electrode, will no longer be affected; The application of DC suppression devices will affect the neutral point current of the transformers nearby.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.