Abstract

Main parameters of IAQ (indoor air quality) could influence people health as well as their ability to learning and work. This research on IAQ was conducted in a classroom of Bialystok University of Technology located in the north-eastern part of Poland. We focused on issues related to indoor temperature, relative humidity, carbon dioxide concentration, air change rates and noise. Indoor temperature was recorded in a range from 23.1 °C to 24.9 °C, so higher than design temperature set at 20 °C or comfort temperature found as average 22 °C [1]. On the other hand, relative humidity was slightly lower than recommended minimum 40 % (range 31.7 % to 38.3 %). Moreover, we found that the concentration of carbon dioxide during the experiment was constantly increasing to final 1067 ppm, while the average air exchange rate was 1.5 h–1.