Abstract

AbstractIt has been observed by the practicing engineers that the inclusion of measurements from phasor measurement units (PMUs), current measurements in particular, into the conventional state estimators (SEs), may deteriorate the numerical performance of the SEs in terms of convergence and accuracy. This paper analyzes the reason for such possible ill‐conditioning of the hybrid SEs that use both conventional and PMU measurements. It presents simplified analytical approaches to identify what causes such ill‐conditioning when PMU measurements are used. The condition number of SE gain matrix may vary depending on the number of the PMUs and its placement in the network. It has been identified that the large difference in weights that are allocated to the traditional measurements and PMU measurements is the main reason of the ill‐conditioning of the hybrid SEs.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.