Abstract

A 1000MW ultra supercritical unit heat consumption rate was higher than design value 324.81 kJ/kW h, in this paper, by comparing the conventional test and assessment test, the result of the analysis of conventional test data at the same time, found out the factors that affect the unit heat consumption, low efficiency of unit mainly include cylinder and putting-in-service proactively reheat steam consumption reduction of warm water, small machine increase, feed water by-pass leakage, system other internal leakage, etc., application of equivalent enthalpy drop method, calculated the influence of the influence factors on the heat consumption of value.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.