Abstract

The vacuum circuit breaker (VCB) is an important vacuum switch widely used in generator protection systems and medium-voltage distribution power systems. For observing the vacuum arc behavior variation and analyzing the dielectric recovery characteristics and interrupting capability of VCBs, an experimental platform for a 40.5-kV/31.5-kA/2500-A VCB was established. Under the condition of typical short-circuit current breaking, the short-circuit current breaking test was carried out and the vacuum arc image was collected to obtain the curve of voltage versus current during the breaking process and the arc resistance distribution. By analyzing the variation trend of dynamic arc resistance, a physical and mathematical description of dynamic arc resistance was obtained by the curve fitting method. By comparing and analyzing the experimental data of arc resistance, it is shown that the physical and mathematical description can appropriately describe the spatiotemporal variation of arc resistance in the arcing interval.