Abstract
A typical district cooling system (DCS) with a chilled water storage system is analyzed in hot summer and cold winter area in China. An analysis method concerning operation modes is proposed based on measured data, which is obtained by long term monitoring and on-site measurements of cooling season. The DCS operates at partial load for a large proportion of the cooling time; in particular, the partial-load rate (PLR) can be less than 25% for more than 50% of the total cooling season. In the night, PLR reaches 5% of the peak load. Thus, it is critical to achieve efficient operation under partial-load conditions of the DCS. Installation of chilled water thermal storage presents a solution to improve the working condition of the DCS and chillers. From the beginning to the end of the cooling season, the DCS operation can be summarized by typical operation modes according to cooling demand and chiller operation. For each mode, the base-load chiller operated at a high-load rate, with an average value of 0.88, and the coefficient of performance (COP) remained in a small range, between 4.2 and 5.2. The average energy efficiency ratio (EER) of the DCS for the cooling season was 3.65 and 3.81 for Years A and B, respectively. With respect to the economics, chillers used 90.2% of off-peak electricity, at only half the price of peak electricity.
Published Version
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.