Abstract

Due to increasing level of power converter-based component and consequently the lack of inertia, automatic generation control (AGC) of interconnected systems is experiencing different challenges. To cope with this challenging issue, a derivative control-based virtual inertia for simulating the dynamic effects of inertia emulations by HVDC (high-voltage direct current) interconnected systems is introduced and reflected in the multi-area AGC system. Derivative control technique is used for higher level applications of inertia emulation. The virtual inertia will add an additional degree of freedom to the system dynamics which makes a considerable improvement on first overshoot responses in addition to damping characteristics of HVDC links. Complete trajectory sensitivities are used to analyse the effects of virtual inertia and derivative control gains on the system stability. The effectiveness of the proposed concept on dynamic improvements is tested through Matlab simulation of two-area test system for different contingencies.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call