Abstract

In order to study the current characteristics of corona discharge in high voltage transmission, the time-domain characteristics and volt ampere characteristics of corona discharge under different high voltage are tested and analyzed. The actual test results show that: in the whole process of corona discharge, with the increase of inter electrode voltage, the frequency of pulse current increases, and the duration of current remains unchanged; negative corona discharge is more likely to occur, and with the increase of voltage, the average current growth rate is higher than positive corona discharge. Under the same interelectrode voltage, the negative corona current is stronger than the positive one. The nonlinearity of equivalent resistance between positive corona discharge electrodes is stronger than that of negative corona discharge.