Abstract
An analysis of soil-structure interaction response of cooling towers was performed based on the frequency domain response. A cooling tower is assumed to rest on a soil layer subjected to an incident earthquake motion. The analytical method makes use of the finite element scheme of a rotational shell and solid elements. In the numerical model, dashpot elements are included at the sides and bottom boundaries, with a natural soil column at the sides. The effects of radiation damping on the horizontal and downward infinite regions, as well as the internal damping of soil layers, are revealed as important, and reduce the response of towers.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.