Abstract

Pipe failure accidents (bursting) are frequent in thermal power plants, and severely influence the safe and economic running of power generation units. The authors analyzed the possible causes and features of coated-after superheater pipe bursting in boilers. Taking the coated-after superheater pipe bursting accident in a power plant for an example, the authors conducted macroscopic topography analysis, running environment analysis, metallurgical analysis, chemical composition analysis and strength analysis of the bulged pipe, ruled out that the coated-after superheater pipe bursting was caused by superheating, and demonstrated that the bursting was caused by crack defect that had not been found during regular inspection

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.