Abstract

The article introduces an abnormal malfunction of YD-A converter oil chromatogram at the low end of UHVDC converter station, through oil chromatography data, ultrasonic positioning, on-site feeding, returning to plant disassembly and simulation calculation, which confirmed that the breakage of the isopotential of the converter electrostatic plate is the cause of the abnormal oil chromatogram and put forward corresponding suggestions and measures.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call