Shift of parameters of the double-tuned AC filter component and failure in prompt correction of detuning frequency may affect the filtering effect of the AC filter. Therefore, this paper studies impedance-frequency characteristics of the double-tuned AC filter according to detuned recording data of the A-typed double-tuned AC filter in the Congxi converter station. It analyzes the variation of the impedance-frequency characteristic curves and relative change rate of resonant frequency as there are deviations between actual values and rated values of each filter capacitance and inductance elements in different degrees, and concludes that variation of the parameter of each element in different degrees may cause different deviations of resonant points of the double-tuned AC filter. MATLAB simulation has proved it can reduce the detuning degree and improve the filtering performance of the filter by adjusting the parameters of the variable reactor to change in the opposite direction of the parameters of the resonant capacitor.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.