Abstract

AbstractEach time switching occurs, a PWM inverter produces high‐frequency leakage currents flowing through stray capacitors. Since the inverter for a trash conveyance crane is installed far away from the motor, the shield power cables between them become long, and leakage currents pass through the stray capacitances of the shielded cables and flow to the ground. This paper proposes a model circuit for analyzing leakage currents which flow into the shields of the cables. The effectiveness of the proposed model circuit is verified by comparison of simulated leakage currents using the proposed method and measured leakage currents. © 2002 Wiley Periodicals, Inc. Electr Eng Jpn, 140(2): 65–72, 2002; Published online in Wiley InterScience (www.interscience.wiley.com). DOI 10.1002/eej.2002