Improving power quality for sensitive load by a Unified Power Quality Conditioner (UPQC) in a distributed generation system is presented in this paper. The power balance of a UPQC, consisting of back-to-back connected series and shunt Active Filters (AF), is analysed. Based on the analysis a novel control scheme is established in a 2-phase Synchronous Rotating d-q Frame (SRF). In this control scheme the series AF is controlled as a current source and makes the input current sinusoidal, while the shunt AF is controlled as a voltage source and keeps the load voltage in the normal value. With the proposed control strategy, the UPQC is capable of compensating not only harmonic and reactive currents of the load but also grid voltage distortion. There is no harmonic interference between harmonic-producing loads and harmonic-sensitive loads, which are connected on the common bus. The performance of a UPQC with the proposed control scheme under nonlinear load and grid voltage distortion is investigated with simulation as well as experimental works.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.