Abstract

The power industry requires regular inspection and meter reading of SF6 gas density in circuit breakers, transformers or gas-insulated switches (GIS) filled with SF6 gas. There is a deviation in the data copied by each operator. The general density meter has a temperature compensation device, but the current product only accurately compensates for the rated pressure value of the device, and the temperature compensation accuracy for other pressure values is poor. The technology involved in this paper is to transmit the density and temperature of SF6 gas in the power equipment to the monitoring background in real time. According to the state equation between SF6 gas temperature, pressure and density, the online value is dynamically compensated in real time on the software. In this paper, the key points of the technology are discussed in depth, which proves its feasibility and practicability.