Abstract

Voltage unbalance typically present in three-phase AC supply systems adversely affects power system components, static converters, drive systems, electric machines, etc., connected to the system. A method to eliminate this unbalance by means of a voltage compensator connected in series with the supply through transformers is described. The technique is based on extracting the negative sequence voltage component of the supply and canceling it in order to obtain balanced voltages. The positive sequence component is then adjusted to achieve voltage regulation. It is shown that the compensation can be achieved with low kilovolt-ampere inverters and that harmonic injection is reduced to a minimum. The authors include implementation principles, design equations, and a design example. Simulated and experimental results confirm the theoretical concept and feasibility of the proposed system.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">&gt;</ETX>

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.