Abstract

There are often some problems during operation of the resonant grounding grid, such as tracking failure, excessive tuning, and oversize residual current caused by compensation not matching grounding fault. A new idea is proposed to solve the problems about using of the neutral voltage detection, analysis and calculation. Firstly, neutral voltage characteristics are analyzed. Secondly, neutral voltage is applied to the calculation of tracking sensitivity, and the problems of tracking failure and excessive tuning are effectively solved. Thirdly, change of operation mode and grid disturbance are distinguished by using characteristics of neutral voltage variation. Lastly, the formulas of neutral voltage ranges are derived, which can distinguish high-resistance grounding fault from low-resistance grounding fault and achieve a smart compensation. This solves the problem of excessive residual current. Simulations verified the above conclusions and the results are satisfied.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.