Abstract

A number of power quality issues including electrical harmonics, poor power factor, and voltage instability and imbalance impact on the efficiency of electrical equipment. To support that equipment operates optimally, electrical power is generated must be have good quality. This study has a purpose to examine the power quality of electrical system AHTS (Anchor Handling Tug Supply) vessel. This research was done by quantitative method. Computational techniques used by the software of Total Harmonic Distortion (THD), which shares characteristics and Electrochemical Impedance Spectroscopy (EIS). The result of this analysis indicated that Electrical system in VM INPOSH REGENT have quality power very good of utility systems during full way condition, however during maneuver, there was a particularly high harmonic from non-linier devices used as motor control, which functional a role propulsion. Based on the result above, it can be concluded that after filtering so that harmonic can correct until perimeter secure ABS standard, system is very good during maneuver long site and maneuver on DP system.

Highlights

  • Computational techniques used by the software of Total Harmonic Distortion (THD), which shares characteristics and Electrochemical Impedance Spectroscopy (EIS)

  • The result of this analysis indicated that Electrical system in VM INPOSH REGENT have quality power very good of utility systems during full way condition, during maneuver, there was a high harmonic from non-linier devices used as motor control, which functional a role propulsion

  • Based on the result above, it can be concluded that after filtering so that harmonic can correct until perimeter secure ABS standard, system is very good during maneuver long site and maneuver on DP system

Read more

Summary

Presented on 3rd ICMET

Com base no resultado acima, pode-se concluir que, após a filtragem, para que a harmônica possa corrigir até o perímetro seguro do padrão ABS, o sistema é muito bom durante o local longo da manobra e a manobra no sistema DP. Palavras-chave: Correção da qualidade de energia; Equipamentos de embarcação; Sistema de energia a bordo; Equipamentos de eficiência; Filtro harmônico

Introduction
Methodology
Results
Harmonics definition
Harmonic distortion
Asses a power quality on ships
Harmonic compensation
Onboard electrical system
Electric system simulation
Final Consideration
Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.