Abstract

SCADA (Supervisory Control and Data Acquisition) system of electricity metering using the internet network aims to monitor electrical energy remotely by utilizing internet services. The system consists of a meter that measures electric quantities acquired by a server located close to the meter. The client reads data acquired by the server through the internet network. The use of internet networks for data transmission generally results in latency time, which affects the validity of the data read by the client, resulting in reduced cumulative power calculation accuracy. In this article, energy calculations using current, voltage and power factor data on the client are compared with the energy value calculated by the power meter. Errors that occur are used to calculate the accuracy of the system. The experiment resulted in latency times ranging from 110 ms - 11219 ms with an average of 572.3025 ms with valid data ranging from 93% of population data and accuracy values ranging from 99.2974% to 99.8648%. The resulting accuracy is within the ANSI C12.20 standard.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.