Abstract

Harmonics is a periodic sine wave distortion, due to the operation of nonlinear loads. Har-monics causes current to flow in the neutral wire even though in a balanced load condition, in addition to harmonic load imbalance problems will increase the current flowing in the neutral wire, making it dangerous for the electrical system. This research was using electrical system modeling simulation in MATLAB application by changing the earth resistance value to see the effect of earth resistance value to Total Harmonic Current Distortion (THDi), it is necessary to analyze the effect of resistance value for THDi neutral wire grounding. This study uses the Fast Fourier Transform (FFT) method. THDi simulation results when the conditions of the resistance value is 9 ?, THDi percentage in phase R is 6.30%, Phase S is 2.86%, Phase T is 2.50%. When the earth resistance value is 5 ?, the percentage of THDi decreases with the value in phase R is 6.09%, Fasa S is 2.61%, Fasa T is 2.48%. When the earth resistance value is 2 ?, the THDi percentage in the R phase is 5.85%, Fasa S is 2.09%, Fasa T is 2.22%. Based on the simulation results it is known that the smaller the earth resistance value, the smaller the harmonic distortion in the electrical system.

Highlights

  • Harmonics is a periodic sine wave distortion, due to the operation of nonlinear loads

  • SCRatio dilakukan per fasa dihitung dengan menggunakan Persamaan 1

  • [10] Janardana, IGN, Pengaruh Umur pada Beberapa Volume Zat Aditif Bentonit Terhadap Nilai Tahanan Pentanahan

Read more

Summary

PENDAHULUAN

Sistem kelistrikan di Fakultas Teknik Universitas Udayana – Sudirman disuplai dari dua buah transformator distribusi 20 kV /380 V salah satunya berkapasitas daya sebesar 100 kVA dan mensuplai kebutuhan beban gedung B, C, D, dan E. Penggunaan beban nonlinier mengakibatkan munculnya permasalahan harmonisa pada sistem kelistrikan di Fakultas Teknik Universitas Udayana – Sudirman. Berdasarkan data hasil pengukuran Total Harmonic Distorstion (THD) arus dan dibandingkan dengan standar IEEE 5192014 maka Nilai THD arus pada transformator yang menyuplai beban gedung B, C, D, dan E yaitu pada fasa R = 9,8 % fasa S = 11,0 % fasa T = 7,5 % [2]. Selain permasalahan harmonisa terdapat permasalahan ketidakseimbangan beban dapat diketahui dari hasil pengukuran yang dilakukan pada kawat netral, mengalir arus sebesar 41,6 A [2].

KAJIAN PUSTAKA
Harmonisa
Sistem Kelistrikan Fakultas Teknik Universitas Udayana – Sudirman
Pemodelan Sistem Tenaga Listrik
Hasil Simulasi THDi Pada Kondisi Nilai Resistansi Pentanahan Berbeda - beda
DAFTAR PUSTAKA
KESIMPULAN

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.