Abstract
In an effort to provide reliable and efficient electrical energy, substations have an important role in regulating the demand for electric power loads and as a center for securing electrical power system components in a certain area. Frequent disturbances become a benchmark for an electric power system whether or not it is good or not in an effort to provide reliable and efficient energy. One of the maintenance measures is temperature measurement using thermal imagers, which is commonly referred to as thermovision measurement.Thermal imager is a tool that can be used for predictive maintenance activities to monitor the condition and performance of an equipment so that the possibility of equipment failure can be minimized. In October 2020, after thermovisiting transformer bay 6 at the Sunyaragi substation, it was discovered that there was a hotspot on the T-phase separation blade, causing heating of the blade, the above conditions can result in a decrease in PMS performance, with the worst condition if left alone can result in damage to the PMS blade and can also melt when the peak load is on the transformer 6. Under these conditions, maintenance is carried out by maintaining contact resistance, insulation resistance, and grounding resistance. The results of the analysis of contact resistance after maintenance show that the equipment is in good condition and still suitable for use, with a value of 7μΩ for the R phase, 6.5μΩ for the S phase, and 6.7μΩ for the T phase.
Highlights
Energi listrik merupakan salah satu kebutuhan manusia yang penting dan tidak dapat dilepaskan dari keperluan sehari-hari
substations have an important role in regulating the demand for electric power loads
Frequent disturbances become a benchmark for an electric power system
Summary
Energi listrik merupakan salah satu kebutuhan manusia yang penting dan tidak dapat dilepaskan dari keperluan sehari-hari. Energi listrik dengan kualitas dan kontinunitas yang baik didapat dengan cara melakukan pemeliharaan secara berkala guna menjaga kondisi setiap peralatan agar dapat mencegah gangguan yang dapat mengakibatkan kerusakan pada sistem [1]. Pada bulan Oktober 2020 setelah melakukan thermovisi pada bay trafo 6 di gardu induk Sunyaragi diketahui terdapat hotspot pada bagian pisau PMS fasa T sehingga menyebabkan pemanasan pada pisau tersebut. Dengan kondisi tersebut di atas dapat mengakibatkan penurunan unjuk kerja PMS, dengan kondisi terburuk apabila di biarkan saja akan mengakibatkan kerusakan pada pisau PMS dan bisa juga meleleh jika saat beban puncak pada trafo 6 itu. Sehingga disimpulkan bahwa PMS dalam kondisi baik dan aman untuk di operasikan
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.