Abstract

A compact multi-layered structure is proposed based on the coiled-up space concept for power transformer noise absorption at 100 and 200 Hz. Current methods of constructing multi-band absorbers are impractical for power transformer noise control due to the high coupling effect deteriorating their performance. To overcome this shortcoming, the proposed structure is composed of multiple connected layers creating two separate coiled ducts with adjustable dimensions to minimise the coupling effect. In the modelling stage, the geometrical features are optimised using the genetic algorithm to maximise the absorption coefficient and minimise the thickness. The proposed dual-tone absorber has a thickness of 43.5 mm which is significantly thinner than the existing conventional absorbers. The measurement results on a 3D-printed structure demonstrate the feasibility of the design.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.