Abstract
This paper presents a method for the optimal design of high voltage transmission lines taking into consideration shielding and backflashover failure rates. The minimization of suitably defined performance indices, which relate the failures caused by lightning in a transmission line to both line insulation level and tower footing resistance, is aimed. Optimum values for both line insulation level and tower footing resistance are calculated. The method is applied on several operating Hellenic transmission lines of 150 and 400 kV, respectively, carefully selected among others, due to their high failure rates during lightning thunderstorms. Special attention has been paid on open loop lines, where a possible failure could bring the system out of service causing significant problems. The obtained design parameters, which reduce the failure rates caused by lightning, are compared with the existing design parameters of the transmission lines leading up to useful conclusions. The proposed optimization method can be proved a valuable tool to the studies of electric power systems designers, intending to reduce the failure rates caused by lightning.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.