Abstract

This paper presents an adaptive optimal control strategy for online control of complex chilled water systems involving intermediate heat exchangers to enhance operation and energy performances. This optimal control strategy determines the optimal settings of the heat exchanger outlet water temperature (hot side) and the required operating number of heat exchangers and pumps in order to minimize the total energy consumption of pumps under varying working conditions. Adaptive method is utilized to update the key parameters of the proposed models online. A simulated virtual platform representing a chilled water system in a super high-rise building was established to validate and evaluate the proposed optimal strategy. Test results show that the strategy has enhanced control robustness and reliability, particularly in avoiding deficit flow problem. Significant energy of chilled water pumps is saved when compared with conventional methods.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.