Abstract

Steady-state power flow calculation belongs to power system steady-state analysis, and the data used in calculation should be steady-state data. However, the existing SCADA system hasnt distinguished the transient data from the steady-state data. The real-time measured data reflect the dynamic electric power system. It is the right reason for not all of the real-time measured power can be used for power flow calculation. In another word, it causes the matching problem between measured data and power flow calculations. Based on the current situation of information collection system, the characteristics of the measured data had been analyzed in this paper. And an effective acquisition method for steady-state measured data is proposed on the theoretical basis of the law of large numbers. It uses the average value of the measured data that in the same load state to approximate the steady-state true value in one period. And the steady-state data can be used in power flow calculation. The simulation results show that the method proposed in this paper ensures the accuracy and reliability of power flow calculation.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.