Abstract

Manufacturers may be required to design transformers to overload specifications. Oil viscosity changes and loss variation with temperature are not accounted for in the industry loading guide. A comprehensive test program was performed using a winding assembly with embedded thermocouples. Steady-state and transient tests were performed for natural and nondirected forced oil calculation. The temperature distribution in the winding was not linear with height as usually assumed. A large number of temperature sensors is required to determine the hot spot location. The location of the hot spot was found to be different and less predictable for natural oil calculation than for nondirected forced oil circulation, especially during overload conditions. Improved loaded guide equations were developed to account for oil viscosity, resistance change, cooling duct oil rise and location of the hot spot. >

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.