Abstract

Airport terminals are key infrastructures with rapid development currently, where the air-conditioning (AC) systems aim to guarantee the normal operation. This research investigated the AC systems in seven Chinese hub airport terminals by a large-scale on-site measurement. The average annual electricity consumption was 177 kWh/(m2 · year), in which 30–60% was consumed by AC systems. The terminal device of AC systems is one of the key components restricting the cooling performance. The commonly used terminal devices (i.e. air handling units) accounted for 40–74% of the AC electricity consumption. As an alternative, the AC system combining radiant floor and displacement ventilation could save 34% of the AC electricity consumption in one investigated airport terminal. Furthermore, the designed cooling capacities were 132–176 W/m2, while the measured values were only 43–90 W/m2. Thus, the AC systems, especially the terminal devices, should have the ability to adjust cooling capacity over a wide range to cope with this prevailing situation of low load rates. This study is beneficial for the design and operation of AC systems in airport terminals.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.