Abstract
Abstract Copper, as one of the most hazardous metals to transformer insulation systems, has attracted a great deal of interest from scholars at home and abroad. Unfortunately, the specific type of copper that causes catalytic aging of oil-paper insulation is still controversial. Therefore, in this paper, the effect of the electronic state evolution of copper in different oxidation states on the aging performance of the insulation systems was investigated by characterization techniques and performance evaluation. Cu2O has a stronger catalytic oxidizing effect on insulation system than CuO. This study elucidates the electronic state evolution of different oxidation states of copper and its influence on the insulation performance, which lays a good foundation for the advancement of transformer fault warning technology.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.