Abstract

High voltage insulators used in various overhead forms are exposed to leakage current and partial discharge. This work deals with different structure forms of insulator, such as (pin post, clamp top and tie top). These structures are applied in different tests, as covered and stripped states. The leakage current for these forms were measured by raising the insulator voltage to (5.25, 6.35, 7.57 kV) for covered and stripped state. Partial discharges were determined in covered and stripped state of these insulator forms using (straight and balanced detection method). Pin post insulators have a leakage current and electric field larger than both clamp top and tie top. The clamp top and tie top insulator show almost the same value of leakage current measurements. The stripped conductors always produce large partial discharge than covered conductor.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.