Abstract
Water treeing is a well known fracture phenomenon in polyethylene (PE) and crosslinked polyethylene (XLPE) high voltage cable insulation. We studied two phenomena: (1) The insulation material is mechanically fatigued by as is shown by measuring the relevant constant, which moreover is compared with literature values on other polymers. The observed electrostriction is found to originate mainly from the Coulomb force. Using a simple model, the deformation mode at the end of a water tree channel can be described and the strain amplitude of the PE at the water interface can be calculated. (2) Under high voltage, the surface tension at the PE-water interface decreases strongly as we found experimentally. The observation that this decrease is proportional to the square of the applied field strength is explained. The joint effect of the Coulomb force and the reduced surface tension may cause a fracture phenomenon, well known in the field of polymers, called environmental fatigue failure (or thermal softening). The same assumption is made as in common environmental stress cracking of PE with aqueous detergents, viz. that the low surface tension plays an essential and not a coincidental role.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.