Abstract
This paper presents a new two-terminal numerical algorithm for fault location estimation using the synchronized phasor in time-domain. The proposed algorithm is also based on the synchronized voltage and current phasor measured from the PMUs(phasor measurement units) installed at both ends of the transmission lines. In this paper the algorithm is given with-out shunt capacitance and with shunt capacitance using 11 -model and estimated using DFT(discrete Fourier transform) and the LES(least error squares method). The algorithm uses a very short data window and classification for real-time transmission line protection. To test the validity of the proposed algorithm, the electro-magnetic transient program (EMTP) and MATLAB is used.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.