As part of a new thermal response test (TRT) and to determine ground thermal conductivities, vertical temperature profiles were obtained using retrievable optical fiber sensors inserted into the U-tubes of two ground heat exchangers (GHEs) installed at Maebaru City (Fukuoka, Kyushu) and Kushiro City (Hokkaido), Japan. Measured profiles and outlet temperatures from TRTs were history-matched with the cylindrical source function. Nonlinear regression was used to estimate the vertical distribution of ground thermal conductivities. The computed distribution is consistent with measured data indicating both the reliability of the optical fiber thermometer and TRT interpretation. It is expected that TRTs and optical fiber thermometers will prove to be increasingly useful for optimizing the depth of the GHEs installed in heterogeneous formations, and consequently will minimize installation costs of geothermal heat pump systems.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.