Abstract

Space vector pulse width modulation (SVPWM) has been extensively utilized in the three-phase voltage source inverters (VSI) for the benefit of fixed switching frequency, full utilization of DC bus voltage and superior control. In recent times, SVPWM technique was applied for active power filter (APF) control application, as the APF is nothing but of a current controlled VSI. The conventional SVPWM based APF has high computational burden due to complex trigonometric calculations and sector identification involved to generate the compensating signal, hence the response time for compensation is slow. In this paper, an improved SVPWM technique based shunt APF is presented based on the effective time concept. The effective time concept eliminates the trigonometric calculations and sector identification, thereby it reduces the computational effort. Simulation results demonstrate the efficacy of the APF with the improved SVPWM based control strategy. The response time for compensation is 0.02sec. Index Terms—SVPWM, shunt APF, VSI

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.