Abstract

This paper proposes an improved power sharing control scheme to achieve the accurate power sharing control and offer an improved PCC voltage regulation capability in islanding microgrid. An enhanced virtual impedance design is assumed in the conventional droop control scheme to manage distributed generation (DG) units to export the accurate reactive power in proportion to their rating. A point of common coupling (PCC) voltage restoration control is implemented to eliminate the PCC voltage deviation produced by the droop control effect and voltage drop effect on the impedance. This control scheme of each individual DG unit was designed to only use the locally measured feedback variables of inverter. It can realize accurate reactive power sharing and guarantee the PCC voltage quality. Matlab simulations are presented to show the effectiveness of proposed control performance in islanding microgrid.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.