Abstract
This paper addresses the issue of improving the conventional iterative method used for integrated extended equal area criterion (IEEAC) and single machine equivalent (SIME) for multi-swing transient stability limit analysis in power system operation. Effects of the complicated phenomena on the conventional method, i.e., nonmonotonic variation of the stability margin and the isolated stability domain (ISD), are studied. Accordingly, the conventional method is improved for both efficiency and accuracy. With this knowledge, an improved sensitivity-based iterative method for searching multi-swing transient stability limit is proposed. The advantage of this method is that the complicated phenomena are fully considered and their effects are either overcome or avoided as much as possible. Case studies on the ten-generator New England power system are presented to verify the effectiveness and efficiency of this improved method.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.