Abstract

In this paper, an improved inverter output filter is proposed for pulsewidth-modulated (PWM) drive systems. The proposed filter is shown to effectively reduce both the differential and common modes dv/dt at the motor terminals, even in the presence of long motor leads. Reducing differential mode dv/dt reduces overvoltages at the motor terminals and lowers the stress on the motor insulation. Lowering common mode dv/dt is shown to significantly reduce high-frequency leakage currents to ground and induced shaft voltage in the motor. An important advantage of the approach is that the filter can be installed within the inverter enclosure to achieve both the differential and common modes dv/dt reductions at the motor terminals. Thus, the use of the filter can contribute to enhanced bearing life and improve reliability of PWM drive systems. Analysis, design equations, and experimental results on a 480-V 20-hp PWM drive system are presented. The filter configuration is an excellent candidate for many new and retrofit PWM 480-V/575-V drive systems.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.